4.6 Automatic re-closing adjusting
This procedure must be carried out ONLY by the installer and ONLY during the setting up of the system.
For a correct programming, before to carrying out any modification, bring always the system in totally closed position (see section 4.2).
Give a step by step order with
automation closed and wait the
complete opening.
Automatic reclosing disabling
Rotate the AUTOMATIC RECLOSING trimmer completely in clockwise
sense. Like this the automatic reclosing is disabled.
Automatic re-closing by photocells
Rotate the AUTOMATIC reclosing trimmer completely in anticlockwise
sense to enable the automatic re-closing by photocells. If the photo-
cells' beam is not interrupted, the control unit recloses after 4 minutes.
WARNING: the automatic re-closing is deactivated if during the closure the intervention of the anti
– squashing sensor happens and the consequent re-opening.
4.7 Re-synchronization
This operation must be carried out ONLY in case you observe repeatedly that the gate does not reach the correct position of closure (or if it tends
to overstep it), or if you find in the conditions described on point 4.8.
The re – synchronization operation consists on the activation in closing of the gate at reduced velocity with the aim to find the point of total closure;
the movement stops itself automatically in the point in which a mechanical stop which obstacles the movement.
Such position is identified as closing position.
Press the first key of the transmitter for a time superior than
6 seconds, then release it.
The gate stops itself temporarily (if in movement), then it
starts again at reduced velocity.
Release the key.
The gate stops itself at the presence of a mechanical stop
memorizing in such as point the close position.
WARNING: during the operation of re – synchronization the intervention of the anti – squashing security is interpreted as identification
of the closing position. To avoid its involuntary intervention the sensitivity of the same results remarkably reduced respect to the normal
condition of functioning.
4.8 Gate unlocking
In case of opening of the gate with inserted lock, it is the intervention of the security which involves the stop of the gate.
In this case it is possible that the lock remains locked cause of the tension exercised by the gate. If this happens it is advisable to resort the re-
synchronizing operation (point 4.7).
4.9 Belt tension adjusting
For an optimal functioning of the control unit and particularly of the anti – squashing security, it is necessary the adjusting of the belt transmitting
the movement.
The adjusting must be carried out in such a way as, during the re-synchronization phase (point 4.7) with trimmer for adjusting the force in position
of normal utilization, the belt does not present slipping or rather making sure that it does not come out from its seat
6-1622356 rev.4 09-07-2013
Rotate the AUTOMATIC RECLOSING trimmer in clockwise sense.
Like this the automatic reclosing time increases.
The automatic reclosing
time is too short.
The automatic reclosing
time is too large.
Rotate the AUTOMATIC RECLOSING trimmer in anti – clockwise
sense. Like this the automatic reclosing time decreases.
Yes
ITA
ENG
FRA
AUTOMATIC
RECLOSING
AUTOMATIC
RECLOSING
NO
ESP
DEU
POR
AUTOMATIC
RECLOSING
AUTOMATIC
RECLOSING