Fault / Alarm
F0239
It indicates interruption in
Profibus DP
the communication between
Interface Offline
the Profibus DP network and
the inverter. The Profibus DP
communication interface went into
offline status.
F0240
It indicates fault in the access to
Profibus DP
the Profibus DP communication
Module Access
module data.
Fault
F0700
No communication with remote
Remote HMI
HMI, but there is no speed
Communication
command or reference for this
Fault
source.
F0710
The SoftPLC user program size
SoftPLC Oversize
exceeds internal memory space.
F0711
There is some failure in the
SoftPLC Program
SoftPLC user program.
Failure
TABLE OF SITUATIONS THE STATUS CONFIG
The CONFIG status is indicated by the HMI "CONF" status, as well as in parameters P0006 and P0680. Such status
indicates that the MW500 cannot enable the output PWM pulses because the inverter configuration is incorrect or
incomplete.
The table below shows the situations of CONFIG status, where the user can identify the origin condition through
parameter P0047.
Quick Reference of Parameters, Alarms and Faults
Description
Possible Causes
Check if the network master is correctly configured
and operating properly.
Check for shor t circuit or poor contact on the
communication cables.
Check if the cables are not misconnected or inverted.
Check if the termination resistors with the right value
were installed only at the end of the main bus.
Check the network installation in general – cabling,
grounding.
Check if the Profibus DP module is correctly fitted.
Hardware errors due to improper handling or
installation of the accessory, for instance, may cause
this fault. If possible, carry out tests by replacing the
communication accessory.
Check if the communication interface with the HMI is
properly configured in parameter P0312.
HMI cable disconnected.
The user application logic is too large, more than 8 kB.
The SoftPLC user program is corrupted.
There was a timeout in the SoftPLC scan.
MW500 | 27