Quick Reference of Parameters, Alarms and Faults
P0047
0
Out of CONFIG status, HMI, P0006 and P0680 must not indicate CONF
1
Two or more DIx (P0263...P0270) programmed for Forward Run (4)
2
Two or more DIx (P0263...P0270) programmed for Reverse Run (5)
3
Two or more DIx (P0263...P0270) programmed for Start (6)
4
Two or more DIx (P0263...P0270) programmed for Stop (7)
5
Two or more DIx (P0263...P0270) programmed for Direction or Rotation (8)
6
Two or more DIx (P0263...P0270) programmed for LOC/REM (9)
7
Two or more DIx (P0263...P0270) programmed for Accelerate E.P. (11)
8
Two or more DIx (P0263...P0270) programmed for Decelerate E.P. (12)
9
Two or more DIx (P0263...P0270) programmed for 2nd Ramp (14)
10
Two or more DIx (P0263...P0270) programmed for PID Man./Auto (22)
11
Two or more DIx (P0263...P0270) programmed for disable Flying Start (24)
12
Two or more DIx (P0263...P0270) programmed for lock programming (26)
13
Two or more DIx (P0263...P0270) programmed for load user 1 (27)
14
Two or more DIx (P0263...P0270) programmed for load user 2 (28)
15
DIx (P0263...P0270) programmed for Forward Run (4) without DIx (P0263...P0270) programmed
for Reverse Run (5) or the opposite
16
DIx (P0263...P0270) programmed for Start (6) without DIx (P0263...P0270) programmed for Stop
(7) or the opposite
17
Reference (P0221 or P0222) programmed for Multispeed (8) without DIx (P0263...P0270)
programmed for Multispeed (13) or the opposite
18
Reference (P0221 or P0222) programmed for electronic potentiometer (7) without DIx
(P0263...P0270) programmed for 11 = Accelerate E.P. or the opposite
19
Run-Stop command (P0224 or P0227) programmed for DIx (1) without DIx (P0263...P0270)
programmed for (1 = Run/Stop) and without DIx (P0263...P0270) programmed for General
Enable (2) and without DIx (P0263...P0270) programmed for Quick Stop (3) and without DIx
(P0263...P0270) programmed for Forward Run (4) and without DIx (P0263...P0270) programmed
for Start (6).
20
Digital input DI2 (P0265) programmed for PTC (29) or analog input AI3 (P0241) programmed
for PTC (4)
21
P0203 programmed for PID via AI1 (1) and reference (P0221 or P0222) programmed for AI1 (1)
22
P0203 programmed for PID via AI3 (2) and reference (P0221 or P0222) programmed for AI3 (3)
23
P0203 programmed for PID via FI (3) and reference (P0221 or P0222) programmed for FI (4)
24
P0203 programmed for PID via AI3 (2) and the plug-in module has no AI3
25
Reference (P0221 or P0222) programmed for AI2 (2) or AI3 (3) and the plug-in module has no
AI2 and AI3
26
P0312 programmed for Remote HMI (0 or 6) without HMI connected
27
Poor configuration of the V/f curve (P0142 to P0147) causes voltage step in the output)
28 | MW500
Situations for CONFIG status
Origin Situation of CONFIG Status