Riello 40 GS10/M Instrucciones Para La Instalación, Uso Y Mantenimiento página 14

Tabla de contenido

Publicidad

Idiomas disponibles

Idiomas disponibles

7.
FAULTS / SOLUTIONS
The control box has a self-diagnostic system, by which it is possible to easily check the faults and find the
solutions.
To use this function, wait for a minimum of 10 sec after the lock out, then push the reset button for 3 sec.
After releasing the button, the RED LED will begin to flash, as shown in the following schedule.
Red fault LED
waiting time 10s
The LED provide a blink code each 3sec.
The blink codes give the information of the possible faults, as follows:
BLINK CODE
2

3

4

5

7

10

In the event of a burner lockout, more than two consecutive burner reset operations could cause da-
mage to the installation. On the third lockout, contact the Aftersales Service.
WARNING
If further lockouts or burner faults occur, interventions must only be made by qualified, authorised per-
sonnel (as indicated in this manual, and in compliance with the laws and regulations currently in force).
DANGER
20067072
Press lockout reset
button for > 3s
The flame does not stabilize at the end of the safety time:
– faulty or soiled ionization probe;
– faulty or soiled fuel valves;
– neutral/phase exchange;
– poor burner regulation.
Minimum air pressure switch does not close:
– air pressure switch faulty;
– air pressure switch incorrectly regulated;
– fan motor does not run;
– maximum air pressure switch operating.
Extraneous light during pre-purging, or control box faulty.
Minimum air pressure switch does not open:
– air pressure switch faulty;
– air pressure switch incorrectly adjusted.
Loss of flame during operation:
– poor burner regulation;
– faulty or soiled fuel valves;
– short circuit between ionization probe and earth.
Control box faulty.
Blink code
Approx. 3s
POSSIBLE CAUSE
12
GB
Blink code

Publicidad

Capítulos

Tabla de contenido
loading

Este manual también es adecuado para:

20066426729t2

Tabla de contenido