Continuation type
Digital outputs
– Rated load voltage
– Design
– Protection against incorrect
polarity
– Output current per channel
– Short circuit protection
– Voltage drop at output
– Output delay
– from "0" to "1"
– from "1" to "0"
– Parallel switching of outputs
for increased performance
– Protection against reverse
voltage
– Limiting the inductive switch-
off voltage of connected
coils/solenoid valves
Electrical isolation
– Between the channels
– For operating voltage supply
for electronics/sensors
(V
)
EL/SEN
Isolation
22
CPX-4DA
4 outputs based on IEC 1131, 24 V
V
(outputs)
OUT
Positive logic (PNP)
Yes
Min. 1 A (24 W lamp load), no sum
current limit
Yes (electronic),
response threshold> 1.0 A
≤ 1 V
With ohmic load:
< 200 µs
< 200 µs
Yes, max. 4 outputs of the same
module
Max. V
OUT
Typ. -16 V
None
Yes, if an intermediate supply is
used
Tested with 500 V DC
Festo CPX-EA 0201NH English