Digital inputs (X210A.3 ... X210B.2):
Low Signal: DC 0 V ... 3 V, High Signal: DC 12 V ... 30 V,
input resistance: 2,3 kΩ, response time: 2 ms , PLC- compatible
Digital output (X210B.3):
Low Signal: DC 0 V... 3 V, High Signal: DC 12 V ... 30 V, maximum output current: 50 mA,
PLC- compatible
Multi-function output (X210B.4):
Analog signal: DC 19 ... 28 V, maximum output current: 50 mA,
pulse width modulated (f
Digital signal: Low Signal: DC 0 V... 3 V, High Signal: DC 12 V ... 30 V,
maximum output current: 50 mA, PLC- compatible, frequency signal: output voltage:
DC 0 V ... 24 V, maximum output current: 40 mA, maximum output frequency: 150 kHz
Multi-function input (X210B.6):
Analog signal: input voltage: DC 0 V ... 10 V (R
input current: DC 0 mA ... 20 mA (R
Digital signal: Low Signal: DC 0 V... 3 V, High Signal: DC 12 V ... 30 V, response time: 4 ms,
PLC- compatible
Conductor cross section:
Suitable conductor cross sections fort he control terminals are:
With wire end ferrule:
Without wire end ferrule: 0,14...1,5 mm²
External 24 V voltage supply
The bidirectional control terminals X210A.1 / X210A.2 can be used as voltage output or voltage
input. If an external 24V voltage supply is connected to the terminals X210A.1/ X210A.2 the
parameterization and communication is possible and inputs and outputs are active, even if the
mains voltage is switched off.
Input voltage range
Input rated current
Inrush current peak
External fuse protection
Safety
Caution!
The digital inputs and the DC 24V terminal of the electronic control equipment can
withstand external voltage up to DC 30V. Higher voltage may destroy the unit.
05/ 2014
Technical data of the control terminals
= 116 Hz),
PWM
=500 Ω),
i
0,25...1,0 mm²;
Requirements of the external voltage supply
DC 24 V ±10%
max. 1,1 A
typical: < 25 A
Via commercial available circuit breakers for rated current,
characteristic: slow acting
Extra safety low voltage (SEL) according to EN 61800-5-1
36
=70 kΩ),
i
Quick Start Guide ACU-P