Before You Begin (cont.)
The valve is calibrated to 104° F (40° C) at the first stop position,
and the maximum temperature limit stop is positioned so the
outlet water temperature does not exceed 120° F (49° C).
Factory calibrated inlet conditions are: Hot and cold water
pressure = 43-1/2 psi (3 kg/cm) Hot water supply temperature
= 149° F (65° C) Cold water supply temperature = 59° F (15° C).
If inlet conditions differ from those used during factory
calibration, it may be necessary to re-calibrate the valve after
installation. The installer must check the mixed flow
temperature after installation, and adjust the valve as needed
according to the instructions.
This valve complies with ASME A112.181M, ASSE 1016, and CSA
B125. The valve is listed with ASSE, CSA, and IAPMO/UPC.
Kohler Co. reserves the right to make revisions in the design of
products without notice, as specified in the price book.