Power measurement
Measuring range
Accuracy
Real energy (IEC 62053-22)
Reactive energy (IEC 62053-23)
Output data
Optional for communication module
Supply
Supply voltage range
Nominal power consumption
Display
Type
Refresh
General data
Dimensions W/H/D
Installation depth without extension module
Installation depth with extension module
Degree of protection
Front
Back
Weight
Electrical isolation
Rated insulation voltage
Measuring device voltage input/measuring device supply
(measuring device U-IN/measuring device POW)
Measuring device voltage input/measuring device cur-
rent input
(measuring device U-IN/measuring device I-IN)
Measuring device current input/measuring device supply
(measuring device I-IN/measuring device POW)
Measuring device voltage input/extension module
(measuring device U-IN/extension module)
Measuring device current input/extension module
(measuring device I-IN/extension module)
Measuring device supply/extension module
(measuring device POW/extension module)
Test voltage
12 PHOENIX CONTACT
0 ... 11 MW/Mvar/MVA
0.5 %
Class 0.5S
Class 2
110 ... 400 V AC ±10 %
120 ... 350 V DC ±20%
< 5 VA (without extension modules)
< 10 VA (with extension modules)
Backlit LCD
1 s
96 x 96 x 82mm
60 mm
80 mm
IP52
IP30
400 g
< 300 V AC (L/N) surge voltage category III
≥ 300 V AC ... 600 V AC surge voltage category II
Safe isolation (EN 61010-1)
Safe isolation (EN 61010-1)
Basic insulation (EN 61010-1)
See extension module
See extension module
See extension module
3.5 kV AC (50 Hz, 1 min.) safe isolation