English
4.2
Mounting
Figure 2
Mounting
To ensure that the device is securely placed on the front panel, the device must be pressed into the mounting slot from
the front and then secured from behind using the four clamps provided.
To mount the device, proceed as follows:
1.
Press the device into the mounting slot from the front and hold it in this position.
2.
Secure the device from behind with the four clamps, as shown in Figure 2.
3.
Push the clamps as far as they will go onto the latch, until the device is securely positioned and the clamps snap
into place.
4.3
Pin assignment
Figure 3
Pin assignment
2
PHOENIX CONTACT
1
IEC/CE
Supply voltage range:
110 ... 400 V AC ±10% at 50/60 Hz
120 ... 350 V DC ±20%
1
UL
Supply voltage range:
110 ... 240 V AC ±10% at 50/60 Hz
120 ... 250 V DC ±10%
2
Fuse:
0.5 A gG/BS 88 2A gG/0.5 A class CC
I1, I2, I3
Measured current connection:
S1 (input)
S2 (output)
V1, V2, V3, VN
Measured voltage connection
104512_en_02