Electrical isolation [...]
Test voltage
Pollution degree
Connection data
Conductor cross section (current)
Conductor cross section (voltage and other)
Connection method
Tightening torque
Ambient conditions
Ambient temperature (operation)
Ambient temperature (storage/transport)
Permissible humidity (operation)
Salt spray
Height
Conformance/approvals
Conformance
UL, USA / Canada
UL-specific data
Supply voltage
Power consumption
Electrical safety
Operating mode
Ambient temperature (operation)
Permissible humidity (operation)
Surge voltages
Surge voltage categories
Surge voltage category of the supply
104512_en_02
2.2 kV AC (50 Hz, 1 min.) basic insulation
2
0.5 mm² ... 6 mm²
0.5 mm² ... 2.5 mm²
Screw connection
0.4 Nm
-10°C ... 55°C (14°F ... 131°F)
-20°C ... +85°C (-4°F ... 185°F)
≤ 95 %
≤ 2.5 %
≤ 2000 m
CE-compliant
U
110 ... 240 V AC ±10 %
120 ... 250 V DC ±10 %
10 VA
UL 61010-1
CSA-C22.2 No. 61010-1
Indoor use
0°C ... 40°C (32°F ... 104°F)
80 % up to 31 °C (87.8 °F)
50 % at 40 °C (104 °F)
Transient surge voltages in acc. with installation classes
I, II, III
min. II