Tal: Time Alarm; Restore Programming And Calibration Parameters - Astralpool MAXI UP Manual De Regulatión

Ocultar thumbs Ver también para MAXI UP:
Tabla de contenido

Publicidad

Idiomas disponibles
  • ES

Idiomas disponibles

  • ESPAÑOL, página 39
HOW TO PROGRAMM THE DELAY ON:

TAL: TIME ALARM

WHAT IS IT'? The Time alarm is expressed in units (0-120units) of dosage. One unit is equivalent to 1 minute of chemical
dosing at 100% of the flow rate. The units counting starts from 0 at the moment when the pump starts dosing after the
power on, it increases during dosing, it stops during level alarm and stand_by state, it is reset when the power supply is
off, when the measure reaches the setpoint, during the flow and broken hose alarm. When the counting reaches the value
of the parameter stored in the Alarm Time, the pump goes into Time Alarm state:
1) The dosing Stops
2) green LED on blinks
3) the display shows: on the second line "Tal" which alternates with the writing of the operating mode and flow rate.
See figure below.
Push ESC / SBY button to bring back the pump in the Operating mode and to reset the count of Time Alarm which re-
starts when the pump starts to dose again.

RESTORE PROGRAMMING AND CALIBRATION PARAMETERS

Attention: the Programming Reset has no influence on Language and Password.
Rev 0.3
In the Utility menu, select "Delay On" by the cursor and press
ENTER.
Use the ▼ ▲ buttons to select the desired minutes of delay
and press ENTER.
Attention: the change will be active from the next power
on of the pump!
If you want to esc programming and return to measurement,
press ESC for 3 seconds.
In the Utility menu, select "TAL" by the cursor and press
ENTER.
Use the ▼ ▲ buttons to select the desired units of dosage
and press ENTER.
If you want to esc programming and return to measurement,
press ESC for 3 seconds.
In the Utility Menu, select "Reset" by the cursor and press
ENTER.
Use the ▼ ▲ keys to display "Yes" on Confirm. Press
ENTER.
With ▼ ▲ keys choose to restore the "Programming
Parameters" or the "Calibration Parameters". Press ENTER.
Automatically the pump restores the factory settings.
Press the ESC button for 3 seconds to exit programming.
Cod. 00.009.157
30

Publicidad

Tabla de contenido
loading

Tabla de contenido