4.2
Installation
Distance from the start of the protective cover to the
height of the measuring diaphragm
Distance from the start of the thread pick-up to the
height of the measuring diaphragm (version without
protective cover)
Figure 4-1
Mounting the pressure transmitter, dimensions in mm
1. Install the pressure transmitter suspended downward on the cable.
2. To prevent measuring errors, fasten the pressure transmitter for moved process media.
3. Fasten the pressure transmitter by means of a guide tube or an additional weight on the transmitter (max. tensile force
on connecting cable 250 N).
4. Fasten the cable above the container with the anchor clamp.
5. Connect the cable itself with the cable box.
6. Mount the cable box at a location appropriate to its degree of protection (IP66) in the vicinity of the measuring point.
7. To ensure proper functioning, make sure that the entry openings on the protective cover of the pressure transmitter do
not get soiled and that the process medium does not freeze.
SITRANS LH100 (7MF1572..) Transmitter for hydrostatic level
A5E32588610-02, 02/2014
Measurement reference height
Level
29