E-100-A
High-Profile End Seal Installation Instructions
APPROVALS
Hazardous Locations
Class I, Div. 2, Groups A, B, C, D
Class II, Div. 2, Groups E, F, G
Class III
– WS
CLI, ZN1, AEx e II T*
Ex e II T*
Ex e IIC T* Gb
E-100-A is IECEx certified for use with:
BTV-CR/BTV-CT:
IECEx
QTVR-CT:
XTV-CT:
KTV-CT:
VPL-CT:
(1)
Except VPL
* For system Temperature Code, see heating cable or design documentation
(2)
Except KTV-CT
KIT CONTENTS
Item
Qty
A
1
B
1
C
1
D
1
WARNING:
This component is an electrical device that
must be installed correctly to ensure proper
operation and to prevent shock or fire. Read
these important warnings and carefully follow all
of the installation instructions.
• To minimize the danger of fire from sustained
electrical arcing if the heating cable is
damaged or improperly installed, and to
comply with the requirements of nVent,
agency certifications, and national electrical
codes, ground-fault equipment protection
must be used. Arcing may not be stopped by
conventional circuit breakers.
(1)
(2)
IECEx BAS 06.0043X
IECEx BAS 06.0045X
IECEx BAS 06.0044X
IECEx BAS 06.0046X
IECEx BAS 06.0048X
.
Description
End seal assembly
Cable lubricant
End seal label
Cable tie
• Component approvals and performance are
based on the use of nVent - specified parts
only. Do not use substitute parts or vinyl
electrical tape.
• The black heating cable core and fibers are
conductive and can short. They must be
properly insulated and kept dry.
• Keep components and heating cable ends dry
before and during installation.
• Bus wires will short if they contact each other.
Keep bus wires separated.
• Use only fire-resistant insulation materials,
such as fiberglass wrap or flame-retardant
foam.
DESCRIPTION
The nVent RAYCHEM E-100-A is a NEMA 4X-rated end seal
kit. It is designed for use with nVent RAYCHEM BTV-CR, BTV-
CT, QTVR-CT, XTV-CT, KTV-CT and VPL-CT industrial parallel
heating cables. Once installed, the end seal is easily re-entered
for maintenance; the heating cable can be accessed without
removing the end seal.
This kit may be installed at temperatures as low as –40°F
(–40°C). For easier installation store above freezing until just
before installation.
For technical support call nVent at (800) 545-6258.
TOOLS REQUIRED
• Wire cutters
• Slotted screwdriver or nutdriver
ADDITIONAL MATERIALS REQUIRED
• nVent RAYCHEM GT-66 or GS-54 glass cloth tape
• Pipe strap
OPTIONAL MATERIALS
• Small pipe adapter for 1 in (25 mm) and smaller pipes:
Catalog number JBS-SPA P/N E90515-000
• For boot replacement order E-100-BOOT-5/PACK P/N 281053-000
Cap
Strain
relief
Boot
Leash
Stand
A
CAUTION:
• Leave these installation instructions with the
user for future use.
HEALTH HAZARD: Prolonged or repeated
contact with the sealant in the end seal
boot may cause skin irritation. Wash hands
thoroughly. Overheating or burning the sealant
will produce fumes that may cause polymer
fume fever. Avoid contamination of cigarettes
or tobacco. Consult MSDS VEN 0058 for further
information.
CHEMTREC 24-hour emergency telephone:
(800) 424-9300
Non-emergency health and safety information:
(800) 545-6258.
• Utility knife
D
C
B