Gree XK46 Manual Del Usuario página 27

Ocultar thumbs Ver también para XK46:
Tabla de contenido

Publicidad

Parame
ter
Parameter name
code
Set address of wired
P13
controller
Set quantity of group
P14
control indoor units
Set unit of
P16
temperature
Set static pressure
P30
of indoor fan motor
Copyright 2018. This translation is property of GREE PRODUCTS SL. All rights reserved. Total or partial reproduction without its express authorization is prohibited.
Defa
Parameter
ult
range
valu
e
01: master wired
controller
01
02: slave wired
controller
00: forbid this
function
01
01-16: indoor
unit quantity
00:Celsius
00
01:Fahrenheit
01-09: static
pressure level of
05
indoor fan motor
23
Wired Controller XK46
Note
When two wired controllers control
one indoor unit (or several indoor
units), the addresses of the two wired
controllers should be different.
Assistant wired controller (02) is
without unit parameter setting
function except setting its address.
Set the corresponding value
according to the connected indoor
unit quantity.
--
There are two kinds of static pressure
level:
5 levels: 03, 04, 05, 06, 07
9 levels: 01, 02, 03, 04, 05, 06, 07,
08, 09
Wired controller can be adapted
to the different types of indoor units
that it possesses 1-9 level selection
for setting static pressure. When the
indoor unit with 5 static pressure
levels received the level setting sent
by wired controller is less than 3, it
will be settled as the 3rd level; if it is
over 7, it will be settled as the 7th
level.