Capacity code of indoor and outdoor units
• For the indoor unit, the capacity code is decided at each capacity rank. (Table 1)
• The capacity codes of the outdoor units are decided at each capacity rank. The maximum number of connectable
indoor units and the total value of capacity codes of the indoor units are also decided. (Table 2-1, Table 2-2)
NOTE
Compared with the capacity code of the outdoor unit, the total value of capacity codes of the connectable
indoor units differs based on the height difference between the indoor units.
• When the height difference between the indoor units is 15 m or less: Up to 200% of the capacity code
(Equivalent to HP) of the outdoor unit.
• When the height difference between the indoor units is over 15 m: Up to 105% of the capacity code.
• If MMU-UP
H is include in the system, total indoor capacity code must be between 50% and 105% of
outdoor unit capacity.
• If the system diversity is more than 135%, check the maximum number of indoor unit connections in table 2-1,
2-2, and then turn on DIP switch 3 of SW103 on the interface P.C. boards.
Table 1
Capacity code
Indoor unit
Equivalent to
capacity rank
Equivalent to HP
capacity
003
0.3
0.9
005
0.6
1.7
007
0.8
2.2
009
1
2.8
012
1.25
3.6
015
1.7
4.5
018
2
5.6
024
2.5
7.1
027
3
8.0
030
3.2
9.0
036
4
11.2
048
5
14.0
056
6
16.0
072
8
22.4
096
10
28.0
125-EN
IM_1141001201-2_Book.indd 63
IM_1141001201-2_Book.indd 63
– 63 –
Table 2-1 [Diversity 135%]
Capacity code
Model name
(MMY-)
Equivalent
[ Standard ]
to HP
MUP0801*
8
MUP1001*
10
MUP1201*
12
MUP1401*
14
MUP1601*
16
MUP1801*
18
MUP2001*
20
MUP2201*
22
MUP2401*
24
UP2611*
26
UP2811*
28
UP3011*
30
UP3211*
32
UP3411*
34
UP3611*
36
UP3811*
38
UP4011*
40
UP4211*
42
UP4411*
44
UP4611*
46
UP4811*
48
UP5011*
50
UP5211*
52
UP5411*
54
UP5611*
56
UP5811*
58
UP6011*
60
UP6211*
62
UP6411*
64
UP6611*
66
UP6811*
68
UP7011*
70
UP7211*
72
UP7411*
74
UP7611*
76
UP7811*
78
UP8011*
80
UP8211*
82
UP8411*
84
UP8611*
86
UP8811*
88
UP9011*
90
UP9211*
92
UP9411*
94
UP9611*
96
UP9811*
98
UP10011*
100
Total
Max. No.
capacity
Equivalent
of indoor
of indoor
units
to capacity
units
22.4
18 (23)
30.2
28.0
22 (28)
37.8
33.5
27 (34)
45.2
40.0
31 (39)
54.0
45.0
36 (46)
60.7
50.4
40 (51)
68.0
56.0
45 (57)
75.6
61.5
49 (62)
83.0
67.0
54 (69)
90.4
73.5
58 (74)
99.2
80.0
63 (80)
108.0
83.9
64 (81)
113.2
89.5
65 (83)
120.8
96.0
66 (84)
129.6
100.5
67 (85)
135.6
107.0
68 (87)
144.4
112.0
69 (88)
151.2
117.4
70 (89)
158.4
123.0
71 (90)
166.0
128.5
72 (92)
173.4
134.0
73 (93)
180.9
140.5
74 (94)
189.6
147.0
75 (96)
198.4
152.0
76 (97)
205.2
156.5
77 (98)
211.2
163.0
78 (99)
220.0
167.5
79 (101)
226.1
174.0
80
234.9
179.0
81
241.6
184.5
82
249.0
190.0
83
256.5
195.5
84
263.9
201.0
85
271.3
207.5
86
280.1
214.0
87
288.9
219.0
88
295.6
223.5
90
301.7
230.0
92
310.5
234.5
94
316.5
241.0
96
325.3
246.0
98
332.1
251.5
100
339.5
257.0
102
346.9
262.5
104
354.3
268.0
106
361.8
274.5
108
370.5
281.0
110
379.3
Diversity
(%)
135%
135%
135%
135%
135%
135%
135%
135%
135%
135%
135%
135%
135%
135%
135%
135%
135%
135%
135%
135%
135%
135%
135%
135%
135%
135%
135%
135%
135%
135%
135%
135%
135%
135%
135%
135%
135%
135%
135%
135%
135%
135%
135%
135%
135%
135%
135%
126-EN
5/2/2564 BE 16:27
5/2/2564 BE 16:27