Rackmount Setup
CAUTION:
The cabinet is heavy (99 kg/218 lb). Always remove both battery trays from the UPS before lifting
the cabinet and installing the UPS on the rails in the rack. Lifting the cabinets into the rack requires a
minimum of two people.
CAUTION:
Installing or removing the batteries should be performed or supervised by personnel
knowledgeable about batteries and the required precautions. Keep unauthorized personnel away from
batteries.
CAUTION:
The batteries are heavy (32 kg/71 lb). Use proper lifting techniques when removing the batteries.
CAUTION:
If installing an optional EBM, the EBM must be located below the UPS with no U space between
the UPS and EBM. This provides better weight distribution in the rack, easier access to the UPS control panel,
and easier routing for the battery cable connections. This also prevents strain between the EBM cord and the
UPS connection and possible connection failure.
WARNING:
For Rack-Mounted Systems: When installing multiple systems in a rack, complete all of the
procedures for the current system before attempting to install the next system.
NOTE:
Mounting rails are required for each individual cabinet.
NOTE:
The cabinet is shipped without the front cover bezel attached.
NOTE:
The following instructions are the same for square-hole racks and unthreaded, round-hole racks. The
rails fit both rack styles.
To install the UPS in a rack:
Ensure that the following are placed on a flat, stable surface near the rack where you will install
1
the UPS:
cabinet
S
two UPS accessory boxes
S
two battery trays (UPS only)
S
two battery retaining brackets (UPS only)
S
Installation and Startup
|
11