Crest factor
Total harmonic
distortion of the
output voltage
Efficiency
Overload capacity
Number of output
phases
Battery charger characteristics
Rated Battery
Voltage
Maximum charge
current
Recharge time
(to 90%)
Communication and management
Screen and signalling
Communications ports
Software
Protections
Mechanical characteristics
Dimensions
W x H x D( mm)
Net weight (kg)
72
3 101 75
3 101 76
< 7% at full non-linear load
up to 94%
106%-120% for 600-30 seconds (linear decrease)
126%-150% for 30-0.16 seconds (linear decrease)
six pushbuttons and five LEDs for real-time control
of the status and the main parameters of the UPS
RS232 and USB (USB not available on 3 101 78)
Connector for network interface
Software for Windows and Linux environments
- displaying all the functioning and diagnostic
- setup of special functions.
Download a copy free of charge from the website
http://www.ups.legrand.com
Electronic circuits against overloads and short-circuit
Emergency Power Off (EPO)
440 x 88 (2U) x 680
25
7 Technical specifications
3 101 77
3:1
< 3% at full linear load
101%-105% continuous
Single phase
240 Vdc
1.86 Adc
4 hours
is available in order to:
data in case of problems;
Backfeed
Overtemperature
440 x 132 (3U) x 680
3 101 78
up to 90%
28