PARAMETER
BUZZER
(this setting can't be
changed with this
procedure)
BATTERY TEST
(this setting can't be
changed with this
procedure)
BYPASS VOLTAGE
RANGE
BYPASS
FREQUENCY
RANGE
SETTING
ON
OFF
OFF
LOW
The bypass voltage range
is set to ±15% of the
selected output voltage
HIGH
The bypass voltage range
is set to ±10% of the
selected output voltage
± 1 Hz
± 3 Hz
If the bypass frequency is
- within the set range: the
output frequency follows
the bypass frequency;
- out of the set range but
within ±10 Hz: the output
frequency follows the
default setting (50 or 60
Hz);
- beyond the default
setting of ±10 Hz: the UPS
turns to stored energy
mode.
DAKER DK Plus
5 kVA - 6 kVA - 10 kVA
DISPLAY
61