ºC
Cut-In
Fuse for Control Circuit
A
Fuse for Fan Unit
A
(Size)
(*) Thermostat of fan motor can not Cut-In automatically. If that cuts out, change the fan motor.
INSTALLATION AND OPERATION MANUAL
KPI-502E1E
KPI-802E1E
KPI-1002E1E
125ºC±10ºC
130ºC±5ºC
150ºC±5ºC
85ºC±10ºC
85ºC±5ºC
100ºC±5ºC
5
5
2(x2)T
2(x2)T
[6X32]
[6X32]
KPI-1502E1E
KPI-2002E1E
155ºC±5ºC
155ºC±5ºC
125ºC±15ºC
125ºC±15ºC
5
5
4(x2)T
4(x2)T
4(x2)T
[6X32]
[6X32]
[6X32]
29
KPI-3002H1E
150ºC±5ºC
100ºC±5ºC
5
5
6(x2)gG
[10X38]