EVAPORATOR PRESSURE

From CALIBRATION, select EVAPORATOR PRESSURE, the following screen is displayed:
Press OK, the following warning message is displayed:
ATTENTION: Automatic Evaporator Pressure calibration can be done only if A/C Pressure is
calibrated and with a minimum of 1 kg of gas inside the bottle.
Press OK to continue:
Make sure that HP and LP couplings are disconnected from A/C system or else, then press OK
to continue:
After few minutes the following message will be displayed:
INSTRUCTIONS MANUAL
R134a
EVAPORATOR PRESSURE
Evaporator pressure
AUTOMATIC CALIBRATION
Press OK
R134a
EVAPORATOR PRESSURE
Automatic Evaporator calibration can be
done only after a PA/C calibration and
with a minimum of 1kg of gas inside the
bottle.
Press OK
R134a
EVAPORATOR PRESSURE
Make sure that HP and LP
couplings are disconnected from
A/C system or else
Press OK to continue
R134a
EVAPORATOR PRESSURE
Evaporator pressure
AUTOMATIC CALIBRATION
Calibration running
Please wait...
PEV AUTOMATIC CALIBRATION
-85-