Sime FORMAT.zip 4 25 OF Manual Del Instalacion página 74

Tabla de contenido

Publicidad

Idiomas disponibles
  • ES

Idiomas disponibles

  • ESPAÑOL, página 26
IT
ES
any air bubbles to be bled off through the
air valves. Should the pressure have risen
PT
well above the limit expected, discharge
the over pressure by opening the pressu-
re-relief valve.
GB
2.5. 1
Emptying the system (fig. 5)
GR
Use the drain tap to empty the system (9).
Turn off the boiler before doing this.
RO
2.6
FLUES/CHIMNEYS
The flue or chimney used to release the
RUS
products of combustion into the atmosphe-
re must comply with current legislation.
2.6. 1
Passing flue pipes through
an existing chimney
When renovating or passing flue pipes
through an existing chimney, use only flues
which are declared suitable for the purpo-
se by the manufacturer, following the
instructions for installation and use provi-
ded by the manufacturer.
2.7
INSTALLATION COAXIAL DUCT
(vers. "25 BF")
The air inlet-smoke outlet assembly ø
60/100 is supplied in a kit code 8084811
complete with mounting instructions.
With the curve supplied in the kit the
maximum horizontal length of the flue
must not exceed 3.4 metres.
The diagrams in fig. 6 illustrate a number of
examples of different coaxial outlets.
2.7. 1
Coaxial flue diaphragm
The boiler is normally supplied with ø 87.5
diaphragm. Insert the diaphragm only if the
length of the coaxial flue.
Refer to fig. 7 for positioning.
72
"25 OF" models
5
8
3 2
4
9
KEY
1 D.H.W. inlet/outlet manifold
2 Fill tap
3 D.H.W. filter
4 By-pass
y
KEY
1
Coaxial flue kit
code 8084811
x + y = max 3,4 m "25"
x + y = max 3,0 m "30-35"
2 a Extension L. 1000
code 8096100
2 b Extension L. 500 code 8096101
3
Vertical extension L. 200 code 8086908
4
Additional 90° curve code 8095800
6
Articulated tile code 8091300
7
Roof outlet terminal L. 1284 code 8091200
8
Vertical condensation collector L. 200 cód. 8092803
IMPORTANT:
– Each additional 90° curve installed reduces the available
length by 0.90 metres.
– Each additional 45° curve installed reduces the available
length by 0.45 metres.
– It is advisable to assemble the condensation collector
(8) on vertical segments exceeding 2.5 metres in length
and to limit maximum length to 4 metres.
With outlet type C12 - C42, install diaphragm ø 87.5 only if the coaxial flue is less
than 1.8 metres long.
With outlet type C32, use the following diaphragms, depending on flue length and without
any additional curves:
Installations with vetrical
extension L. 200 code 8086908
Optional
Standard
diaphragm ø 86 diaphragm ø 87,5
(cód. 6028623)
L min = 1,3 m
L min = 2,5 m
L max = 2,5 m
L max = 4 m
"25 BF" models
8
5
2
1
3
5 Water rate adjuster
6 D.H.W. exchanger
7 Microswitches
8 Water flow switch
9 Boiler discharge
x
2
4
3
C42
C32
max 3,4 m "25"
max 3,0 m "30-35"
C12
Installations with vertical condensation
collector code 8092803
Without
Standard
diaphragm
diaphragm ø 87,5
L min = 4 m
L max = 2,5 m
L max = 5 m
7 6
4
9
Fig. 5
7
6
2
8
3
1
Fig. 6
None
diaphragm
L min = 2,5 m
L max = 4 m
Fig. 7

Hide quick links:

Publicidad

Tabla de contenido
loading

Este manual también es adecuado para:

Format.zip 4 25 bf

Tabla de contenido