Main Menu &
Sub Menu Function
Code
DHW Code
Domestic Hot Water Tank
30
Heat Pump
Booster Heater
Disinfection
Forced DHW operation
Solar Panel/DHW Thermostat
Direction of DHW valve
DHW Application
The FSV #3011 in the wired remote controller should be set to "1(Yes)" to use DHW function.
Heat Pump Variables for Controlling DHW Tank
• Maximum DHW tank temperature with R-410A(refrigerant) heat pump operation : FSV #3021, Default 50˚C,
Range : 45 ~ 50˚C.
• Temperature di erence determining the heat pump OFF temperature : FSV #3022, Default 2˚C, Range : 2 ~ 10˚C.
• Temperature di erence determining the heat pump ON temperature : FSV #3023, Default 5˚C, Range : 5 ~ 20˚C.
• DHW heating mode timer : Mode timer manage the operation terms when there are simultaneous requests of space
- FSV #3024(minimum Space heating operating time, Default 5 min., Range 1 ~ 20 min.), #3025(maximum DHW time,
Default 30 min., Range 5 ~ 95 min.), #3026(maximum space heating operation time, Default 3 hour, Range 0.5 ~
10 hour)
- Maximum operation time is applied only when both DHW and Space heating request operation. DHW or Space heating
operates continuously until reaching at target temperature without time limitation in the single operation.
• The FSV #4011 for DHW priority should be set to "0(DHW)"(Default). Space heating gets a priority by setting FSV
#4011 "1", but this is only valid when the outdoor temperature is lower than the speci ed temperature de ned
NOTE
by FSV #4012.
Field Setting Value
Description
Application
Max Temp
Stop
Start
Min. Space heating operation
time
Max. DHW operation time
Max. Space heating operation
time
Application
Delay Time
Overshoot
Compensation Temp
Application
Interval
Start Time
Target Temp
Duration
Max time
Timer OFF Function
Timer Duration
H/P Combination
DHW Tank
heating/cooling and DHW.
ENGLISH-43
Sub
Default
Min
Code
11
0(No)
0
21
50
45
22
2
2
23
5
5
24
5
1
25
30
5
26
3
0.5
31
1(On)
0(O )
32
20
20
33
0
0
34
10
0
41
1(On)
0(o )
42
Fri(5)
Sun(0)
43
23
0
44
70
40
45
10
5
46
8
1
51
0(O )
0
52
6
3
61
0
0
71 0(Room)
0
1(Tank)
Max
Step
Unit
1(Yes)
-
-
50
1
˚C
10
1
˚C
20
1
˚C
20
1
min
95
5
min
10
0.5
hour
1
-
-
95
5
min
4
1
˚C
20
1
˚C
1
-
-
All(7)
1
day
23
1
o'clock
70
5
˚C
60
5
min
24
1
hour
1(On)
-
-
(x10)
30
1
min
2
1
-
-
-