9. Control Panel
9.1 Introduction/Operation
To Turn ON the UPS:
Once all modules are assembled and installation cabling is complete:
1. Switch ON Internal/External Battery Breakers.
2. Switch ON Main Input Breaker (Q1) located on the front of the breaker panel (the LCD panel will display "Bypass Mode").
3. Press the Power button
4. Switch ON Output Breaker (Q3). Parameters can now be viewed, adjusted and programmed via the control panel located on the front of the
UPS system.
To Turn OFF the UPS:
WARNING
The UPS system shutdown procedure will eliminate the AC power output for all loads. Before shutdown, confirm all loads
are turned off.
1. Press the Power button
2. UPS will transfer to Bypass Mode or Standby mode if bypass is disabled.
Note: UPS will have no output when in Standby Mode.
3. Switch OFF Output Breaker (Q3).
4. Switch OFF Main Input Breaker (Q1).
5. Wait 1 minute and then shut off battery breakers.
Note: To be fully de-energized, UPS must be disconnected from AC input.
The Control Panel is the user control and interface for all measured parameters, UPS and battery status and alarms and is divided into three
areas:
1
LCD Display – Graphic display and all measured parameters
2
LED Indicators – refer to table 9.1
3
Control Keys – refer to table 9.2
LED
INPUT
BYPASS
INVERTER
BATTERY
ALARM
16-11-183-9334F8.indb 19
for 2 seconds; the UPS is now in "Line Mode".
for 2 seconds.
Color
Green
Amber
Green
Red
Red
1
3
Status
On
Flashing
Off
On
Flashing
Off
On
Off
On
Flashing
Off
On
Flashing
Off
Table 9.1
19
Figure 9.1
Definition
Input source is normal
Input source is abnormal
No input source
Load is on bypass
Input source is abnormal
Bypass is not functioning
Load is on inverter
Inverter is not functioning
Load is on battery
Low battery
Normal operation, battery is charging
UPS fault
UPS alarm
No alarms