7. Installation
The Power Module's LED indicator displays its operational status as follows
No.
Behavior
1
Indicates the system is abnormal
2
Indicates the parallel system is abnormal
3
Normal operation of the primary UPS
4
Normal operation of the subordinate UPS

7.2.2 Removing a Power Module

WARNING
Before removing any Power Module, ensure the remaining Power Modules can support the attached load and the UPS is
in Line or Bypass mode.
1. Place the ready switch on the front panel of the Power Module to the
2. The Power Module FAULT LED (RED) will be lit to indicate the Power Module output is off and disconnected from UPS.
3. Wait 5 minutes after unlocking the power module to service.
4. Remove the four screws from the fixing bracket.
5. Fully remove the Power Module from the frame.
Notes:
• The Power Module is heavy; two people are required to remove it.
• When a power module is removed from the frame, the "Redundancy Set Fail" alarm will sound. Refer to Section 9.3.6.2: System to adjust the Total Power and
Redundancy settings based on power modules removed.
To replace a Power Module, refer to the procedure in Section 11.1: Power Module Replacement.

7.2.3 Installing a Battery Module

Each Battery Module is comprised of of four battery trays. Trays are shipped separately in individual boxes (four boxes per module), fully
assembled. Refer to Section 9.3.6.3: Battery for instructions on configuring Amp Hour rating when adding battery modules. The default is 9Ah.
For Medium and Small Frames, each additional battery module installed (4 x trays) is 9Ah.
1. Insert battery tray into open slot in the frame position and slide into cabinet, ensuring the +/- connectors make full contact.
2. Secure each battery tray with two screws (provided in accessory bag).

7.2.4 Removing a Battery Module

Remove two bottom screws on front panel of the battery tray and pull out the battery module using the handle provided.
16-11-183-9334F8.indb 16
LED Display
FAULT – constant red LED
FAULT – flashing red LED
POWER – flashing green LED
POWER – constant green LED
unlocked position by rotating the knob anticlockwise.