Cim 1Xx Profibus Module; Installation; Connecting The Profibus; Cim 1Xx Profibus-Modulet (Cim = Communication Interface Module), Som Er En Profibus-Slave, Giver - Grundfos CIM 1 Serie Instrucciones De Instalación Y Funcionamiento

Tabla de contenido

Publicidad

Idiomas disponibles
  • ES

Idiomas disponibles

  • ESPAÑOL, página 27

2.1 CIM 1XX Profibus module

1
2
3 4
Fig. 1
CIM 1XX Profibus module
Pos. Designation
1
B (RxD/TxD-P)
2
A (RxD/TxD-N)
3
DGND
4
VP
5
SW1/SW2
6
LED1
7
LED2
8
SW3
9
SW4
The power supply (pos. 4, fig. 1) must only
Note
be used for external termination.
8
9
5
6
7
Description
Profibus terminal B
(positive data signal)
Profibus terminal A
(negative data signal)
Profibus terminal DGND
(external termination)
+5 VDC
(external termination)
On/off switches for
termination resistors
Red/green status LED for
Profibus communication
Red/green status LED for
internal communication
between the CIM 1XX
and the Grundfos product
Hex switch for setting the
Profibus address (four
most significant bits)
Hex switch for setting the
Profibus address (four
least significant bits)

3. Installation

Warning
The CIM 1XX must only be connected to
SELV or SELV-E circuits.

3.1 Connecting the Profibus

Grundfos recommends to use a cable according to
IEC 61158.
Example
Siemens, 6XV1 830-0EH10.
Cable length
Maximum cable length
Kbits/s
[m/ft]
9.6
1200/4000
19.2
1200/4000
45.45
1200/4000
93.75
1000/3300
187.5
1000/3300
500
400/1300
1500
200/660
3000
100/330
6000
100/330
12000
100/330
Fitting the cable
Procedure:
See fig. 2.
1. Connect the red conductor(s) to terminal B
(pos. 1).
2. Connect the green conductor(s) to terminal A
(pos. 2).
3. Connect the cable screens to earth via the earth
clamp (pos. 3).
It is important to connect the screen to
earth through the earth clamp and to
Note
connect the screen to earth in all units
connected to the bus line.
5

Publicidad

Tabla de contenido
loading

Tabla de contenido