1SFC101047M9701
Noti ce.
This product has been designed for environment A. Use of this product in environment B may cause unwanted electromagnetic disturbances
in which case the user may be required to take adequate mitigation measures.
Hinweis e.
Dies ist ein Produkt für Umgebung A. In Haushaltsumgebung kann dieses Gerät unerwünschte Funkstörungen verursachen; in diesem Fall kann
Noti ce.
Ce produit a été conçu pour environnement A. L'utilisation de ce produit dans environnement B peut causer des perturbations électro-
magnétiques non désirées qui, dans ce cas, peuvent obliger l'utilisateur à prendre des mesures d'atténuation appropriées.
Obs.
Den här produkten har konstruerats för miljöklass A. Användning av produkten i miljöklass B kan förorsaka oönskade elektromagnetiska
störningar och i så fall krävs att användaren vidtar nödvändiga åtgärder.
Avvertenza. Questo prodotto è stato progettato per l'ambiente A. L'uso di questo prodotto nell'ambiente B può provocare disturbi elettromagnetici
indesiderati, nel qual caso l'utilizzatore può dover prendere adeguate misure per loro attenuazione.
Nota.
Este producto ha sido diseñado para ambientes A. El uso de este producto en ambientes B puede causar perturbaciones electromagnéticas
no deseadas, en tal caso el usuario tendrá que tomar las medidas de mitigación adecuadas.
本产品适用于环境 A, 在环境 B 中使用本产品会产生有害电磁干扰, 在此情况下用户需采取适当防护措施.
警告!
.
M12
45 N.m - 398 lb.in
A1
A2
2050
=
1000
Ith=
A
Ui
V DC
1
2050
1000
Ie DC-
=
A
Ue
=
V DC
60947-4-1
IEC
EN
60947-4-1
3
All
poles must be
connected in se ries
Device eq uipped with
permman ent mag nets
.
According to UL 60947- 4 - 1
GAF1650: Use terminal kit K7TK, wire 4/0 AWG - 500 kcmil, Cu 75° C only, 375 in - lb.
GAF2050: At 2100A 1000V DC, use copper bars each of minimum four busbars per terminal
All contactors: * Designed for max 40° C surround temperature.
Pozidriv N° 2
M 3,5
ø 5
1 Nm (7 in. lbs)
2//LP 2050
2050-10
GAF
.
2
inch(width) by 1/4 inch (thickness). Three poles connected in series.
1/2
Cu 75°C
For series connection of contactor poles with
LP connection strips LP2050, use the derated
current according to this table.
Maximum continuous current with 2//LP2050
connection strips per pole.
Contact
G)AF1650
(
G)AF2050
(
+
.
2
2 x 1 ................... 2,5 mm
2
2 x 0,75 ............. 2,5 mm
/ > 3,5 mm, L < 8 mm
le_max
or
1350 A
1650 A
For series connection of contactor poles,
To minimize terminal temperatures,
length of connection should be at
least 0,5m / pole.
Use connection bars/cables dimensions
acc. to brochure 1SFC101004B0201,
or main catalogue.
4/7
100 mm