Interconnection
Direct Connection
2-Wire Extension
Coaxial Extension
Note:
Grounding transducer as shown is mandatory per safety regulations and for
isolation against electrical interference.
Installation
•
Installation shall only be performed by qualified personnel and in accordance with local
governing regulations.
•
Do not route cable openly; instead run cable separately in a grounded metal conduit to
protect it from ambient electrical noise.
•
Seal all thread connections to prevent the ingress of moisture.
•
Do not run cable near high voltage or current runs, contactors or SCR control drives.
•
For pressure tight applications, install transducers hand tight plus ½ turn to 1½ turns.
PTFE tape or other appropriate sealant may be used to aid in sealing the threads for use
in pressure applications.
WARNING:
Improper installation may result in loss of process pressure.
7ML19985QS81
XLT Series Transducers – OPERATION MANUAL
Siemens Milltronics controller (typical)
blk
blk/hot
wht/shld
wht
junction
box
blk
drain/shield
wht
extend cable using 18 AWG shielded/twisted pair
extend cable using RG - 62 A/U coax for optimum
signal to noise ratio
Page EN-7