Mounting Instructions - SICK microScan3 Manual De Instrucciones

Ocultar thumbs Ver también para microScan3:
Tabla de contenido

Publicidad

Idiomas disponibles
  • ES

Idiomas disponibles

  • ESPAÑOL, página 12

MOUNTING INSTRUCTIONS

1
Mounting using mounting kit 1
2
Mounting using mounting kit 2
6
M O U N T I N G I N S T R U C T I O N S | microScan3 mounting kits
All rights reserved. Subject to change without notice.
Mounting kit 1:
1
The mounting kit is available as mounting kit 1a without protection for the optics cover
and as mounting kit 1b with protection for the optics cover.
Tool required:
TX20 Torx wrench
1.
Make sure that the mounting bracket 1 is oriented correctly. See the symbol on
the mounting bracket.
2.
Mount the mounting bracket 1 on the mounting surface.
3.
Push the safety laser scanner onto the mounted mounting bracket 1.
4.
Use all 4 supplied M5 screws 3 to fix the safety laser scanner on the mounting
bracket 1.
5.
Tighten the M5 screws. Tightening torque: 4.5 Nm to 5.0 Nm.
Mounting kit 2:
2
You will also need mounting kit 1a or 1b for mounting using mounting kit 2.
Mounting kit 2 consists of two parts: holding plate 6 and alignment bracket 4.
The mounting kit is available as mounting kit 2a with low depth and as mounting kit 2b
with greater depth. Mounting kit 2b is recommended if the system plug is being
mounted on the back of the safety laser scanner and angled plug connectors are being
used.
Tool required:
TX20 Torx wrench
1.
Make sure that the holding plate 6 is oriented correctly. See the symbol on the
holding plate.
2.
Mount the holding plate 6 on the mounting surface. Either use the two outer drill
holes à or the two drill holes with countersink ß. Also use the drill hole in the
holding tab 9.
Procedure when using the drill holes with countersink ß:
w
Loosen the screws 7 and remove the alignment bracket 4 from the holding
plate 6.
w
Mount the holding plate 6 on the mounting surface.
w
Make sure that the alignment bracket 4 is oriented correctly. See the symbol
on the alignment bracket.
w
Push the alignment bracket 4 back onto the centering pin 8 and fix it on the
holding plate 6 using the M4 screws, washers and spring rings 7.
3.
Make sure that the mounting bracket 1a 1 or 1b is oriented correctly. See the
symbol on the mounting bracket.
4.
Use the supplied M4 screws, washers and spring rings5 to fix mounting bracket
1a 1 or 1b on the alignment bracket4.
5.
Only with mounting kit 2b: an additional stabilization screw is needed if there are
stricter requirements on vibration/shock resistance. Turn the stabilization screw
with washers and spring rings á into the thread hole of the holding plate 6
through the slot of the alignment bracket 4.
6.
Push the safety laser scanner onto the mounted mounting bracket 1.
8017780/ZMJ3/2017-05-17 | SICK
Subject to change without notice

Publicidad

Tabla de contenido
loading

Tabla de contenido