2 Product Data and Operating Range

(1) See the Data Sheet for detailed product data. Data on the product nameplate always takes
precedence. If there is any special requirement, consult the local sales office for model
selection.
(2) maximum and minimum water operating pressures.
The maximum inlet water pressure is 1.0×10
The minimum inlet water pressure is 0.2×10
(3) Operating Range
Item
Cooling
Heating (Heat Pump)
Item
Cooling
Heating (Heat Pump)
Copyright 2018. This translation is property of GREE PRODUCTS SL. All rights reserved. Total or partial reproduction without its express authorization is prohibited.
D Series Modular Air-cooled Scroll Chillers Owner's Manual
Fig.1-1 Schematic Diagram
Water Side
Leaving Water
Water Flow
Temperature
3
m
/ (h·kW)
(℃ )
7
0.172
45
Water Side
Leaving Water
Temperature
(℃ )
5 ~ 15
40 ~ 50
6
Pa.
6
Pa.
DB Temperature
(℃ )
35
7
Chilled Water
Temperature Difference
(℃ )
2.5 ~ 6
2.5 ~ 6
2
Air Side
WB Temperature
(℃ )
6
Air Side
Ambient DB
Temperature
(℃ )
15 ~ 48(R22)
15 ~ 45(R410A)
-15 ~ 24