Chiller: Data Available - Hitachi HARC-MODBUS Manual De Instalación Y Funcionamiento

Tabla de contenido

Publicidad

Idiomas disponibles
  • ES

Idiomas disponibles

  • ESPAÑOL, página 20

6.2 CHILLER: Data available

Address
Name
0
EXIST
1
SYSTEM_ADDRESS
2
(Not used)
3
ONOFF_SET
4
MODE_SET
5
TEMP_SET_C
6
TEMP_SET_H
7
CENTRAL_SET
8
ONOFF_STATUS
9
MODE_STATUS
10
TEMP_C_STATUS
11
TEMP_H_STATUS
12
WATER_INLET
13
WATER_OUTLET
14
AMBIENT_TEMPERATURE Ambient temperature
15
OPER_CONDITION
16
ERROR_CODE_CH
17~22
ERROR_CODE_CYC
23~31
(Not used)
Notes:
– Offset Position is: 40000 + N*32 + Address as shown in table, where N is Water Chiller Address.
– Status (real value) and Set (value ordered) parameters have usually the same value but, in some cases, some of them can be
different. It is recommended to use Set parameters for normal control.
– *) When Temperature Setting and Operation Mode are changed at the same time, order first the operation mode change and
later set the desired temperature.
PMML0175A-rev.1 - 6/2008
HARC-MODBUS - xxxxxxxxxxxxxxxx
HARC-MODBUS - Installation Manual
Description
Exist
Chiller Address
(Not used)
On/Off setting order:
Mode Setting order
COOL setting temperature
HEAT setting temperature
Central Setting
On/Off Status
Mode Status
COOL Setting Temperature
Status
HEAT Setting Temperature
Status
Inlet temperature
Outlet temperature
Unit operation condition
Alarm code for general
CHILLER alarm
Alarm code for cycle alarm
(1~6)
(Not used)
Values
Read/Write
0: Not exist
Read
1: Exist
0~ 15 in H-LINK 1
Read
(Not used)
(Not used)
0: Stop
Read/Write
1: Run
0: Cool
Read/Write
1: Heat
(see note *)
Read/Write
0: Local
Read/Write
1: Remote
0: Off
Read
1: On
0: Cool
Read
1: Heat
Read
Read
Read
Read
Read
0: OFF
Read
1: Thermo OFF
2: Thermo ON
3: Alarm
Read
Read
(Not used)
(Not used)
15

Publicidad

Tabla de contenido
loading

Tabla de contenido