HARC-MODBUS - Installation Manual
12
HARC-MODBUS - xxxxxxxxxxxxxxxxxx
6. Operation
6.1 PACKAGED: Data available
Address
Name
(Note 1)
0
EXIST
1
SYSTEM_ADDRESS
2
UNIT_ADDRESS
3
SET_ONOFF
4
SET_MODE
5
SET_FAN
6
SET_TSET
7
SET_LOUVER
8
SET_CENTRAL
9
READ_ONOFF
10
READ_MODE
11
READ_FAN
12
READ_TSET
13
READ_LOUVER
14~18
(Not used)
19
ERROR_CODE
20~21
(Not used)
22
OPER_CONDITION
23~31
(Not used)
Note 1: Offset Position is: 20000 + N*32 + Address as shown in table, where N is Indoor Unit Address.
Description
EXIST:
0: Not exist
1: Exist
System Address:
0 ~ 15 in H-LINK 1
Unit Address:
0 ~ 15 in H-LINK1
On/Off setting order:
0: Stop
1: Run
Mode Setting order:
0: Cool
1: Dry
2: Fan
3: Heat
4: Auto
Fan Setting order:
0: Low
1: Medium
2: High
Setting Temperature: 17ºC ~ 30ºC
Louver Setting:
0 ~ 8 (8 is Auto)
Central Setting
Bit 0: On/Off (always can be stopped)
Bit 1: Mode
Bit 2: Setting Temp
Bit 3: Fan
On/Off Read:
0: Off
1: On
Mode Read
0: Cool
1: Dry
2: Fan
3: Heat
4: Auto
Fan Read
0: Low
1: Medium
2: High
Setting Temperature Read
(17ºC to 30ºC)
Louver Read
0 ~ 8 (8 is Auto)
(Not used)
Alarm Code
(Not used)
Unit Operation Condition
0: OFF
1: Thermo OFF
2: Thermo ON
3: Alarm
(Not used)
Read/Write
Read
Read
Read
Read/Write
Read/Write
Read/Write
Read/Write
Read/Write
Read/Write
Read
Read
Read
Read
Read
(Not used)
Read
(Not used)
Read
(Not used)
PMML0175A-rev.1 - 6/2008