Dew Point Verification - Ingersoll Rand HRD Serie Manuel De Instrucciones

Secadores de aire comprimido
Tabla de contenido

Publicidad

Idiomas disponibles

Idiomas disponibles

DANGER
Do not remove the petcock base from the
shuttle valve.
• Unscrew and remove the petcock wing from the
petcock base on the shuttle valve at the top of
the dryer (see Figure 5).
• Insert a
-inch allen wrench through the pet-
3
16
cock base to the set screw.
• Adjust the set screw until the pressure on the
purge gauge corresponds to the desired purge
rate as indicated on the purge flow calibration
graph. Turn the set screw counterclockwise to
increase the
purge flow;
clockwise to de-
crease the purge
flow.
• Remove the allen
wrench.
• Replace the pet-
cock wing.
Model
30
HRD56
21
HRD100
39
HRD160
62
HRD200
78
HRD275
107
HRD350
136
HRD475
185
HRD600
234
HRD800
312
HRD1000
390
HRD1200
468
HRD1450
565
HRD1710
666
HRD2010
783
HRD2250
877
HRD2600
1013
HRD3250
1267
Average Purge Rate
38.5
(% inlet air)
Maximum inlet air pressure, 150 psig. Higher pressures available as an option on some models; consult your local distributor
1
HRD Series (Bulletin 348)
Figure 5
Cutaway of Shuttle Valve
INLET AIRFLOW AT VARIOUS INLET AIR PRESSURES
40
50
60
Average Inlet Airflow (scfm)
26
31
36
48
56
65
76
90
104
95
113
130
131
155
179
167
197
228
227
268
309
286
338
391
382
451
521
477
564
651
572
677
782
691
818
944
815
965
1114
959
1134
1309
1073
1269
1465
1240
1467
1693
1550
1833
2117
31.5
26.6
23.0
Inlet air temperatures higher than 100°F will
reduce the design dew point of the dryer.
The dryer can now be put into service. No further ad-
justments are necessary unless there are changes in op-
erating conditions. Within limits, changes in inlet flow
rate can be compensated for by adjusting the purge ad-
justment valve (repeat Steps 1 through 5 above).

Dew Point Verification

After the dryer has operated for a minimum of five
days, check the dew point of the outlet air with a pres-
sure dew point instrument. Follow the directions for
the instrument used. For extremely low dew points al-
low the probe to dry for up to 24 hours after inserting
it into the airstream. It may take up to two weeks of
dryer operation to stabilize at dew points in the –80°F
to –100°F range.
Use only metallic tubing when checking dew point
since plastics, rubber and similar materials absorb
moisture from the ambient air and give false readings.
Table 3
Inlet Air Pressure (psig)
70
80
90
41
45
50
74
83
91
118
132
146
148
165
183
203
227
251
258
289
319
351
392
434
443
495
548
591
661
730
738
826
913
886
991
1095
1071
1197
1324
1263
1412
1561
1484
1660
1835
1662
1858
2054
1920
2147
2373
2400
2683
2967
20.3
18.2
16.4
CAUTION
1
100
110
125
2
55
60
67
100
109
122
160
174
195
200
217
244
275
299
335
350
381
426
475
516
579
600
652
731
800
870
974
1000
1087
1218
1200
1305
1462
1450
1576
1766
1710
1859
2083
2010
2185
2448
2250
2446
2740
2600
2827
3167
3250
3533
3958
15.0
13.8
12.3
150
79
144
230
287
395
503
682
862
1149
1436
1723
2082
2455
2886
3231
3733
4667
10.4
1-9

Publicidad