Colonia 3 - Mini Colonia
English
Problem
Condensation
The
temperature of
the cabinet is
too high or too
low
Water leaks,
bad odour
in the cabinet
Presence of
in the evaporator
frost or
ice
46
Possible causes
poor environmental conditions
circulation of air is inadequate
the heating elements of the
glass parts are not working
the glass panels are not
correctly closed
poor environmental conditions
the outlet air temperature is
not within the specifications
provided
the cabinet is in the process of
defrosting.
the condenser or the
evaporator are freezing.
the load is not evenly
distributed
the condenser or the
evaporator is clogged or dirty.
the drainage parts of the
cabinet are blocked or
damaged
the drip tray is not correctly
sealed
the drip tray is full
there are no gaskets between
the cabinets in channel or they
are not correctly sealed
the fans are not working
resistance breakage
Sdef probe detachment
Possible solutions
check the position of the cabinet in the
premises (cap.13.)
check operation of the fans and the
electrical connections
check the electrical connections
check operation of the heating
elements
close the glass panels well
check the position of the cabinet in the
premises (cap.13.)
check operation of the evaporator fan
check the electrical connections and
the input voltage
the fans are installed contrarily, check
and reset the direction of air flow
check that the plenum of the fan is
sufficient and unimpeded
check that the suction pressure is
within the factory specifications
check the defrost settings
ensure the suction section is not
blocked
reload the goods in an orderly manner
(Fig. 17)
proceed to clean (cap.21.4.)
unblock the drainage part
repair or replace the drainage parts
seal correctly
check the electrical connection to the
evaporation resistance
check operation of the evaporation
resistance
install and seal the gaskets
check the electrical connections
check operation of the heating
elements
check the position of the Sdef probe
(cap.15.)