3 • INSTALLATION / ASSEMBLY / CONNECTION
Before installing the device, observe the following:
• Before installing the product, switch off the power supply.
• Information concerning the motion detector's range is based on an
GB
installation height of 3 m.
• The greater the installation height, the wider the range, but the lower
the sensitivity.
• Movement diagonal to the detector is optimal for triggering the
detector (a direct and head­on approach is more difficult and
therefore the range is significantly reduced.)
• The detector should be positioned according to spatial conditions
and requirements.
• Make sure that the detector has a clear line of sight, as infrared
beams cannot penetrate solid objects.
The presence detector features two separate DIMMER light channels.
Both light channels are synchronised (C1 = C2) in the factory settings.
Light channel C2 can be switched on after light channel C1.
Remember to bear this in mind when assigning lighting groups to the
channels. We recommend that you assign the "room interior" lighting
group to light channel C1 and the "window side" lighting group to
channel C2. Nevertheless, it is still possible to mount the presence
detector on the ceiling in any orientation (Fig. 2).
ESYLUX PD-C360i/24 DUODIMplus presence detectors are
composed of a power and a sensor section. Install the power section in
the required position (Fig. 3) and connect the presence detector as per
the circuit diagram (Fig. 4).
14
Standard operation
Standard operation with additional control by means of a button
Master/slave connection for presence detectors: a maximum of 10 slave
devices can be connected to the master device
As an option, settings can be performed using the DIP switch on the
back of the sensor (see DIP switch section). This must be done before
the device is activated. Plug the sensor section into the power section
and gently screw in place.
4 • START-UP
Connect the power supply
• A warm-up phase of approx. 25 seconds is initiated.
The red (light channel 1 = C1), green (light channel 2 = C2) and blue LEDs
flash alternately. During the process, the connected lighting is
switched on.
The detectors are preset to factory settings P1/remote control and are
therefore immediately ready for use after the warm­up phase.