Exit programming mode
Blue LED goes out; the settings are now saved. The
detector will now operate automatically according
to the preset values.
NOTE: If programming mode is not exited by
pressing the button, the detector automatically
exits programming mode 10 minutes after the last
button was pressed.
Selecting the channel to be programmed
Acknowledgement:
C1 = red and blue LEDs flash
C2 = green and blue LEDs flash
C3 = blue LED flashes
By pressing the "DIM" button once, the dimmer
begins periodically and automatically to gradually
adjust the lighting's light intensity between the
max. and min. values. When the required ambient
brightness level is reached, press the "Eye" button.
The new brightness set value is saved.
Setting the brightness set value (100 Lux – 750 Lux)
Acknowledgement: red and blue LEDs flash three times,
automatic light control to the set value.
Setting the brightness set value to 100 % luminous efficiency
Acknowledgement: red and blue LEDs flash three times,
no lighting adjustment, 100 % light depending on
presence.
Time setting C1 + C2
If no movement is detected, the time setting starts.
Time setting C3
If no movement is detected, the time setting starts.
Orientation light value 10 % – 40 % + "ON"
When pressed for the first time, the orientation light
is set to 10 %. Each further press increases the value
by another 10 % until 40 % is reached. The value
then starts again at 10 %.
If no further buttons are pressed, the nightlight
feature is activated.
Orientation light afterglow duration
After the orientation light value has been set, the
time for the afterglow feature is set.
Orientation light "OFF"
GB
19