However, if the ambient lighting level is brighter than the preset target
value, the light channels are controlled to 100 % of the luminous
efficiency. They remain on while movement is being detected,
regardless of the ambient lighting level.
HVAC channel C3 is switched on regardless of the ambient light value, but
depending on detected movement. If movement is no longer detected,
the time settings for the respective channels start. As an option, each
channel can be manually switched on or off using buttons S1 – S3.
Semi-automatic mode HVAC channel C3
Depending on the preset light value and detection of movement, light
channels 1 + 2 switch on automatically. They remain on for as long as
movement is detected and for as long as the ambient light value does
not exceed the respective target value.
HVAC channel C3: Manual light activation using button S3, no automatic
activation. If movement is no longer detected, the time settings for the
respective channels start. As an option, each channel can be manually
switched on or off using buttons S1 – S3.
Semi-automatic mode ECO light channel C1 – C2
Manual light activation using button S1, no automatic activation. If
the ambient lighting level is darker than the set target value, the light
channels are controlled according to the preset target value. They
remain on for as long as movement is detected and for as long as
the ambient light value does not exceed the respective target value.
However, if the ambient lighting level is brighter than the preset target
value, the light channels are set to the orientation light value and switch
off after the set time has elapsed, regardless of whether motion is
detected or not. If, light is required however, the required brightness
value must be set using button S1 before the time setting expires.
In this case, the activated light channels remain on for as long as
movement is detected, regardless of the ambient lighting level.
HVAC channel C3 is switched on regardless of the ambient light value, but
depending on detected movement. If movement is no longer detected,
the time settings for the respective channels start. As an option, each
channel can be manually switched on or off using buttons S1 – S3.
Semi-automatic mode corridor light channel C1 – C2
Manual light activation using button S1, no automatic activation. If
the ambient lighting level is darker than the set target value, the light
channels are controlled according to the preset target value. They
remain on for as long as movement is detected and for as long as
the ambient light value does not exceed the respective target value.
However, if the ambient lighting level is brighter than the preset target
value, the light channels are controlled to 100 % of the luminous
efficiency. They remain on while movement is being detected,
regardless of the ambient lighting level.
HVAC channel C3 is switched on regardless of the ambient light value, but
depending on detected movement. If movement is no longer detected,
the time settings for the respective channels start. Light channels C1 + C2
cannot be switched off with a button. HVAC channel C3 can be manually
switched off using button S3.
Orientation light
The orientation light is an adjustable basic light. The luminous
efficiency can be set from 10 % to 40 % of the full luminous efficiency.
GB
17