1006
Alarm 2
1007
Alarm 3
1008
Setpoint gradient
Relay status (0 = Off, 1 = On):
Bit 0 = Relay Q1
1009
Bit 1 = Relay Q2
Bit 2 = Reserved
Bit 3 = SSR
1010
Heating output percentage (0-10000)
1011
Cooling output percentage (0-10000)
Alarms status (0 = None, 1 = Active)
1012
Bit 0 = Alarm
Manual reset: write 0 to reset all alarms.
1013
In reading (0 = Not resettable, 1 = Resettable)
Bit 0 = Alarm 1
Error flags
Bit 0 = Eeprom writing error
Bit 1 = Eeprom reading error
Bit 2 = Cold junction error
Bit 3 = Process error (sensor)
1014
Bit 4 = Generic error
Bit 5 = Hardware error
Bit 6 = L.B.A.O. error
Bit 7 = L.B.A.C. error
Bit 8 = Missing calibration data error
1015
Cold junction temperature (degrees.tenths)
Start / Stop
1016
0 = Controller in STOP
1 = Controller in START
Lock conversion ON / OFF
1017
0 = Lock conversion OFF
1 = Lock conversion ON
Tuning ON / OFF
1018
0 = Tuning OFF
1019
Automatic / manual selection 0 = Automatic
1020
C.T. current ON (Ampere with tenths)
1021
C.T. current OFF (Ampere with tenths)
1022
OFF LINE* time (milliseconds)
1023
Instant Current (Ampere)
1024
Digital Input State
Gestione Tune per loop di regolazione 1
With automatic Tune (par. 73
0= autotuning function OFF
1= autotuning in corso
With manual Tune (par. 73
0= autotuning function OFF
1025
1= autotuning ON
With synchronized Tune (par. 73
0= autotuning function OFF
1= command output OFF (forza il raffreddamento)
2= command output ON (forza il riscaldamento)
3= autotuning ON
4= autotuning finished
1026
Zero tare AI1 (1 = tare; 2 = reset tare)
30 - ATR244 - User manual
1 Bit 1 = Alarm
2 Bit 2 = Alarm 3
Bit 1 = Alarm 2
Bit 2 = Alarm 3
1 = Tuning ON
= Auto):
tun.1
=
tun.1
manu.
=
tun.1
or
):
OncE
):
SYncH.
R/W EEPROM
R/W EEPROM
RO
EEPROM
RO
0
R/W 0
RO
0
RO
0
R/W 0
RO
0
RO
-
R/W 0
R/W 0
R/W 0
R/W 0
RO
0
RO
0
R/W -
RO
0
RO
0
RO
0
R/W 0
R/W 0
R/W 0