controller does not return to START automatically: for this operation, the user's
intervention is required.
256 d. i . 4 .c.
Digital Input 4 Contact
Defines the resting contact of the digital input 4.
Normally open (Default)
n.open
257 d. i . 4 .P.
Digital Input 4 Process
Select the size related to the digital input 4.
Value read on input AI1. (Default)
A.in.1
Value read on input AI2.
A.in.2
Arithmetic average of the value read on inputs AI1 and AI2 [(AI1-AI2)/2].
MEAn
Difference of the values read on inputs AI1 and AI2 (AI1-AI2).
diFF .
Module of the difference of the values read on inputs AI1 and AI2 (|AI1-AI2|).
Ab.dif .
Sum of values read on inputs AI1 and AI2 (AI1+AI2).
SuM
258 d. i . 4 .r.
Digital Input 4 Reference Command
Defines the reference command for the digital input 4 functions.
Command 1 (Default)
cmd. 1
Command 2
cmd. 2
Command 1 and 2
cmd.1.2
259÷262
Reserved Parameters - Group P
Reserved parameters - Group P
GROUP Q -
sft.s
263 Pr.cY.
Pre-programmed Cycle
Enables special functionings.
Disabled (Default)
diSab.
Enabled (all remote setpoint functions are inhibited)
Enab.
264 SS.TY.
Soft-Start Type
Enables and selects the soft-start type
Disabled (Default)
diSab.
Gradient
Grad.
Percentage (only with pre-programmed cycle disabled)
Perc.
265 ss.r.c.
Soft-Start Reference Command (only on ATR244-23XX-T)
Defines the reference command for the Soft-Start and the pre-programmed cycle.
Command 1 (Default)
cmd. 1
Command 2
cmd. 2
Command 1 and 2
cmd.1.2
266 SS.Gr.
Soft-Start Gradient
Rising/falling gradient for soft-start and pre-programmed cycle.
0..20000 Digit/hour
267 SS.Pe.
Soft-Start Percentage
Output percentage during soft-start function.
0..100%. (Default: 50%)
268 SS.tH.
Soft-Start Threshold
Threshold under which the soft-start percentage function is activated, at starting.
-9999...30000 [digit
64 - ATR244 - User manual
- Soft-start and mini cycle
(degrees.tenths/hour if temperature). (Default: 100.0)
1 p. 74
] (degrees.tenths for temp. sensors) (Default: 1000)
1 p. 74
Normally closed
n.cLos.