Energi Savr Node
Sample application: preconfigured mode requires no setup
Zone 3
Daylight
Sensor
Room 2
Room 1
Daylight
Sensor

Out of Box Functionality

This section describes the default functionality that the unit will
present when first installed.
Inputs (Occupancy, Daylight, and IR):
• Input group A: controls zones 1 and 2.
• Input group B: controls zones 3 and 4.
Occupancy Sensors (Occ)
• Corresponding zones will turn on when the occupancy sensor is in
the occupied state (closed) and off when in the unoccupied state
(open).
Daylight Sensors (Photo)
• When used in conjunction with a Lutron
corresponding zones will turn on when light sensed by daylight
sensor falls below the factory preset level (if occupancy sensor
indicates that area is occupied).
• QSNE-4S10-D only: Corresponding zones will turn off when light
sensed by daylight sensor rises above the factory preset level.
• QSNE-4T10-D only: Corresponding zone light levels will raise or
lower when light sensed by daylight sensor falls below or rises
above a factory default setting.
IR Receivers (IR)
• See IR Receiver literature for compatible transmitters.
• Corresponding zones respond to on, off, and Scene commands
from compatible IR transmitters.
• QSNE-4T10-D only: Corresponding zones respond to Raise and
Lower commands from compatible IR transmitters.
Lutron
10
|
®
QS for 0-10 V / Switching
TM
ESN QS
Wired to
unit
input group
B
Occupancy
Sensor
Zone 1
Wired to input
group A
Occupancy
Sensor
occupancy sensor,
®
|
Wired to
input group
B
Zone 2
seeTouch
QS Wallstations
®
• All seeTouch
QS lighting wallstations are Scene keypads by
®
default.
• QSNE-4S10-D only: Scenes 1-16 will turn all the lights on.
• QSNE-4T10-D only: Scenes 1-16 will dim lights to the preset
levels in the table below:
Scene #
Light Level: All Zones
1, 5-16
100%
2
75%
3
50%
4
25%
• Scene Off will turn all the lights off.
Contact Closure Input (CCI)
• The CCI behaves as an Emergency Contact Closure Input.
• If the CCI input is open, the ESN QS unit will enter Emergency
Mode, which will turn on all loads and disable local zone control
and control from sensors and QS devices.
• When the CCI is closed or jumpered, ESN QS unit zones will
return to the settings or levels they were at prior to entering
Emergency Mode.
Energi Savr Node
TM
Installation Guide
Zone 4
QS for 0-10 V / Switching Installation Guide