Energi Savr Node
Product overview
The 0-10 V / Switching Energi Savr Node
maximum of 10 AX per zone. An ESN QS system consists of an ESN QS unit, lighting loads, inputs, wallstations, and QS interface
devices. The diagram on the previous page shows a typical system topology.
• All lighting loads are powered through the ESN QS unit.
• The ESN QS unit is limited to:
– 2 Lutron
wired daylight sensors (models: EC-DIR-WH)
®
– 2 Lutron
wired occupancy sensors (models: Lutron
®
– 2 Lutron
wired infrared (IR) receivers (models: EC-DIR-WH, EC-IR-WH)
®
– 1 emergency contact closure input (defaults to Emergency Mode in the absence of a contact closure across the input)
• The ESN QS unit is limited to:
– 16 total wired or wireless occupancy sensors across all 4 zone outputs
– 1 wired or wireless daylight sensor per zone
• The QS Link can have up to 100 zones and 100 devices.
• The ESN QS unit counts as 1 device and 4 zones on the QS Link.
• In a system with multiple ESN QS units on a QS Link, a maximum of 100 daylight sensors, 100 occupancy sensors, 100 IR receivers,
and 100 Pico
wireless controllers are permitted.
®
• The ESN QS unit supplies up to 14 Power Draw Units (PDUs) for powering accessory QS devices. Refer to accessory device
documentation for power draw information.
Wiring overview
QSNE-4T10-D
PELV
Contact
Input
Input
Closure
Group A
Group B
Input
Mains Wiring
Lutron
2
|
®
QS for 0-10 V / Switching
TM
(ESN) QS unit can control up to four zones or circuits of lighting, switching up to a
TM
LOS series)
®
0-10 V Channels
Zone
Zone
1 Zone
3 Zone
QS
2
4
Link
Zone
Zone
Zone
Zone
1
2
3
4
Load power and switched outputs
|
Installation Guide
QSNE-4S10-D
PELV
Contact
Input
Input
Closure
Group A
Group B
Input
Mains Wiring
Energi Savr Node
QS for 0-10 V / Switching Installation Guide
TM
QS
Link
Zone
Zone
Zone
Zone
1
2
3
4
Load power and switched outputs