7. Push the probe to the correct depth. The correct depth depends on where the installation
valve is located: radiator pipe or transformer wall.
• Valve in radiator pipe: Install the probe so that the back of the weather shield is
180 ... 190 mm from the pipe surface.
• Valve in transformer wall: Install the probe so that the back of the weather shield is
200 mm from the transformer wall.
When the probe is in the correct depth, turn the transmitter 90 degrees two to three
times to remove any air bubbles from the sensor area.
14
200 mm
DANGER!
Severe risk of death and of damage to transformer:
Pay attention to transmitter installation depth and possible energized
parts inside the power transformer to minimize electric shock hazard
and equipment damage.
180 ... 190 mm
M211736EN-D