3. Service and maintenance

ALL ADJUSTMENTS DESCRIBED IN THIS CHAPTER CAN ONLY BE CARRIED
B
OUT BY QUALIFIED PERSONNEL.

3.1 Adjustments

Gas conversion

The unit can work with 2
the unit. If the unit has to be used with a gas other than the factory-set one, proceed as follows:
1. Disconnect the power supply and turn off the gas.
2. Remove the front panel (see *** 'Opening the front casing and sealed chamber panel' on page 244 ***).
3. Turn the Throttle (fig. 30) according to the position indicated in table 9.
4. Apply the plate for LPG (contained in the document bag) near the technical data plate.
5. Refit the front panel and turn on the power to the boiler.
6. Modify the parameter for the type of gas:
Put the boiler in standby mode and press the Reset button (detail 6 - fig. 1) for 10 seconds.
The display shows 100 and the text "co" flashing; press the "Heating +" button (detail 4 - fig. 1) to set and dis-
play 120.
Then press the "DHW +" button (detail 2 - fig. 1) to set 123.
Press the Reset button once (detail 6 - fig. 1).
The display shows tS flashing; press the "Heating +" button once (detail 4 - fig. 1).
The display shows Sc flashing; press the Reset button once (detail 6 - fig. 1).
The display shows Sc alternating with 01 flashing;
Press the DHW buttons to set the parameter as per table 9.
press the "Heating +" button (detail 4 - fig. 1).
The display shows Sc alternating with 02 flashing;
Press the Reset button (detail 6 - fig. 1) for 10 seconds; the boiler returns to standby.
The fan will be activated for about 20 seconds.
Turn on the gas.
7. MAKE SURE THE FRONT PANEL OF THE SEALED CHAMBER IS CLOSED AND THE INTAKE/FUME EX-
HAUST DUCTS ARE COMPLETELY ASSEMBLED
Put the boiler in heating or DHW mode (by drawing hot water) for at least 2 minutes. During this period the boiler
performs a calibration and the flame symbol flashes on the display. The end of calibration is indicated by the flame
symbol steady on the display.
Check the combustion values (see following par.).