RC(S)(L)(D)
6.1
Error and warning indication
I
NOTE
All faults are indicated by a warning symbol, a fault ID and a beep. The
beeping lasts for 2 minutes and is repeated every 30 minutes until the
error has been rectified.
RC10.4T.70, RC10.4T.90, RCL10.4(E)T, RCD10.5(X)T, RCS10.5(X)T
Faults are indicated by a fault code with a warning symbol (
TFT display.
If multiple faults occur, the fault codes scroll over in the middle of the display.
All faults of the WARNING (W) type are reset automatically once the fault has been
rectified.
All faults of the ERROR (E) type must be reset manually:
➤ Press the control knob for at least 2 seconds.
✔ A beep sounds.
✔ The error has been reset.
Code
Audio alarm
W02
E03
W04
W10
W11
W19
E32
E33
E34
E35
EN
Fault
No
Defective temperature sen-
sor in the refrigerator com-
partment
Yes
Communication error
No
CI bus fault
Yes
Door open for more than
2 minutes
Yes
DC voltage <7.5 V
Yes
DC voltage <10.9 V
Yes
Outer fan overcurrent
Yes
Compressor does not start
Yes
Compressor overload
Yes
Thermal cut out compressor
controller unit
Troubleshooting
) in the middle of the
Solution
➤ Contact an authorized cus-
tomer service point.
➤ Press the on/off button for at
least 2 seconds.
Resets automatically
➤ Close the door.
Resets automatically
Resets automatically
➤ Press the on/off button for at
least 2 seconds.
➤ Press the on/off button for at
least 2 seconds.
➤ Press the on/off button for at
least 2 seconds.
➤ Press the on/off button for at
least 2 seconds.
19