• Flexible conduit from the oven should be connected directly to the junction box.
• Fuse both sides of the line.
• Do not cut the conduit. The length of conduit provided is for serviceability of the oven.
• A UL listed or CSA approved conduit connector must be provided.
• If the house has aluminum wiring, follow the procedure below:
1.
Connect a section of solid copper wire to the ends of the flexible conduit leads.
2.
Connect the aluminum wiring to the added section of copper wire using special
connectors and/or tools designed and UL listed for joining copper to aluminum.
Follow the electrical connector manufacturer's recommended procedure. Aluminum/
copper connection must conform with local codes and industry accepted wiring
practices.
For power requirements for models DOB30M977D*, and DOB30M977S*, refer to the
following table.
Model
DOB30M977S*
DOB30M977D*
NW9000K_MOD_DOB30M977DS_DG68-00923A-01_EN+MES+CFR.indb 19
240 VAC
Power
Circuit size
5.6 kW
30 Amp
11.2 kW
50 Amp
208 VAC
Power
Circuit size
4.2 kW
30 Amp
8.4 kW
50 Amp
English 19