P R ER EQ UISITE S FOR INSTALLATION .
DANGER
Working on electric installations without proper precautions will result
in the risk of electric shock, and thus cause severe injury or death.
• The installation must only be performed by qualified electricians.
• Make sure that connection of the electrical power cannot occur during installation.
• Put up caution tape and warning signs to mark the working areas.
Make sure no unauthorized persons enter the working areas.
CHOOSE LOCATION.
• Position the wallbox, where possible, in surroundings where it is not exposed
to extreme sunlight and vulnerable to external damage.
• The wall must have a flat structure and must be able to hold a load of at least 100 kg.
• The minimum free space around the wallbox must be a minimum of 300 mm.
NOTE
The below illustration indicates a standard installation height.
Observe and comply with the local accessibility regulations.
Pre-installation checklist.
• The local installation regulations are identified and are followed.
• A miniature circuit breaker (MCB) and residual current device (RCD) must be installed
upstream and have ratings that correspond to the local power supply as well as to the
required charging power.
• The following installation instructions are obeyed.
• The recommended tools (additional tools needed) are available on site.
See chapter Tools and material needed for more information.
• The plugs, screws, and drill bits to be used for mounting the wall bracket are suitable
for the wall structure at the place of installation.
• The bending radius of the power supply cable is within tolerances
during and after installation.
2 0