A SSEM B L E WA LL BOX .
See the corresponding illustrations
B 5.4
in manual B.
1. Install power supply cable.
CAUTION
Using stranded wires without ferrules may
result in improper installation, which can cause
accelerated aging of electric components and/
or loss of electric connection.
• Use crimped insulated ferrules
for 1-phase installation.
• Use crimped uninsulated ferrules
for 3-phase installation.
a. Strip the outer insulation of the cable to a
length of 50 mm, then strip the individual
wires to 12 mm.
b. Route the cables to their connection
terminals. Ensure that the bending radius
is within the limits for the cable type.
c. Connect the wires according to the
CUPRA Charger model and the color
coding table below.
A. CUPRA Charger Pro with kWh meter.
a. Connect L1 (as well as L2 and L3 - for
3-phase version) wire(s) of the power
supply cable to L1, L2, L3 terminals
of kWh meter.
b. Connect Neutral (N) wire of the power
supply cable to the N feed-through
terminal, located next to the kWh meter.
c. Connect PE wire of the power supply
cable to the first available slot of the
PE feed-through terminal, located next
to the kWh meter.
B. CUPRA Charger and CUPRA Charger
Connect without kWh meter:
a. Connect L1 (and L2 and L3 - for 3-phase
version) wire(s) of the power supply cable
to L1, L2, L3 slots of the feed-through
terminals.
b. Connect Neutral (N) wire of the power
supply cable to the N feed-through terminal.
c. Connect PE wire of the power supply cable
to the first available slot of the PE feed-
through terminal.
COLOR CODING FOR POWER SUPPLY CABLE
Wires
L1
L2
Color
Brown Black
NOTE
If the wallbox is not equipped with feed-through
terminals or a kWh meter, strip the individual
wires to 15 mm (1-phase wallbox) or 10 mm
(3-phase wallbox). Afterwards, connect the
supply cable wires directly to the connection
terminals on the lower central part of the power
board according to the stated color coding.
2. Optionally, install and connect the CT
coil cable.
a. Strip the outer insulation of the cable to a
length Wof 50 mm, then strip the individual
wires to 7 mm.
b. Connect the signal wires.
L3
N
PE
Green/
Grey
Blue
Yellow
2 9