7 Installing the AC-CON
5. Remove all connecting screws of the AC-CON
(TX20). Note for STP 8000TL / STP 10000TL / STP
12000TL / STP 15000TL / STP 17000TL: Screws
that are no longer relevant for the equipment of the
new assembly may be installed within the indicated
area.
6. Remove the assembly.
7
Installing the AC-CON
Compatibility of assemblies
The assemblies of the spare-part set NR-STP200-ACCON and NR3-STP200-ACCON are not
compatible with the TP-ACCON-XX.XX assembly.
• Before replacing the assembly, ensure that the assembly is only replaced with a
compatible assembly. Refer to the assembly's type label to find out which assembly is
installed in the inverter.
There are sections on this assembly with a safety extra-low voltage circuit (SELV circuit). To ensure
the safety of the circuits, an optical inspection must be carried out before installation.
24
STP8-17-STP15-20TLEE-AC-CON-RM-xx-10
SMA Solar Technology AG
Replacement Manual