FLARED CONNECTIONS
• This unit has flared connections on both indoor and outdoor sides.
• Refrigerant pipes are used to connect the indoor and outdoor units as shown in the figure below.
• Insulate both refrigerant and drain piping completely to prevent condensation.
Limits
Pipe length
25 m max.
Height difference
10 m max.
No. of bends
10 max.
• Refrigerant adjustment ... If pipe length exceeds 7 m, additional refrigerant (R410A) charge is required.
(The outdoor unit is charged with refrigerant for 7 m pipe length.)
7 m maximum
Pipe length
Exceeding 7 m
PIPING PREPARATION
1 Table below shows the specifications of pipes commercially available.
Pipe
Outside diameter
For liquid
6.35 mm
For gas
15.88 mm
• Use a copper pipe or a copper-alloy seamless pipe with a thickness of 0.8 mm (for ø6.35) or 1.0 mm (for
ø15.88). Never use any pipe with a thickness less than 0.8 mm (for ø6.35) or 1.0 mm (for ø15.88), as the
pressure resistance is insufficient.
2 Ensure that the 2 refrigerant pipes are well insulated to prevent condensation.
3 Refrigerant pipe bending radius must be 100 mm or more.
Caution:
Be sure to use the insulation of specified thickness. Excessive thickness may cause incorrect installa-
tion of the indoor unit and lack of thickness may cause dew drippage.
No additional charge required
Additional charge required
Refrigerant to be added 20 g/m
Insulation thickness
Insulation material
8 mm
Heat resisting foam plastic
8 mm
0.045 specific gravity

4. INDOOR UNIT INSTALLATION

4-1
A CASE OF SUSPENDING INDOOR UNIT FROM THE CEILING
4-1-(1)
MOUNTING INSTALLATION PLATE FIXING BOLTS
1. Determine the locations of installation plate fixing bolts.
• Use installation pattern to determine the locations of instal-
lation plate fixing bolts J.
a Installation pattern
Details are printed on pattern.
Attention:
Surrounding temperature and humidity conditions
may cause paper pattern to shrink or expand.
(Measure dimensions before drilling holes.)
2. Suspension structure (Give site of suspension strong struc-
ture).
I Wood structure
• Select tie beam (one-story houses) or second-floor
girder (two story houses) as reinforcement member.
• Use sturdy beams of at least 60 mm square for beam
pitch of 900 mm or less or of at least 90 mm square for
beam pitch of 900-1800 mm.
a Pitch
b Ceiling
c Rafter
d Bracket
e Roof beam
I Ferroconcrete Structures
• Secure installation plate fixing bolts J as shown at the
right or use angle-stock bracework to install installa-
tion plate fixing bolts J.
f Use inserts rated at 100-150 kg each
g Steel reinforcing rod
J Installation plate fixing bolts
3. Installation plate fixing bolts pitch.
• Use the installation plate fixing bolts J M10 (× 4 procure
locally).
a Indoor unit
b Air outlet
1 Installation plate
• Projecting dimension of installation fixing bolts J from hori-
zontal base line against which you fix installation plate 1
as within at the right.
c Horizontal base line
1 Installation plate
J Installation fixing bolts
4
a
*Remove installation pattern after installation.
a
a
e
b
d
c
g
f
J
1065 mm
150 mm
300 mm
1
b
a
c
max. 40 mm
J
1