3
Installation
DANGER: Risk of electric shock!
▶ Before installing this product: completely
disconnect heat appliances and all other
BUS nodes from the mains voltage.
▶ Before commissioning: fit the cover
( Fig. 17, page 96).
3.1
Preparation for installation in the heat source
▶ Refer to the installation instructions of the heat source to
determine whether modules (such as the MM100) can be
installed in the heat source.
▶ If the module can be installed in the heat source without a
mounting rail, prepare the module ( Fig. 3 and 5,
page 92).
▶ If the module can be installed in the heat source with a
mounting rail, refer to Fig. 8 and 11, page 94.
3.2
Installation
▶ Install the module on a wall ( Fig. 3 to Fig. 7, page 93 and
page 14), on a mounting rail ( Fig. 8, page 93), or in a
heat source. When installing the module in a heat source,
please follow the instructions for the heat source.
▶ When removing the module from the mounting rail, refer to
Fig. 8 on page 93.
▶ Install the flow temperature sensor in the assigned heating
circuit with mixer.
3.3
Electrical connection
▶ Observe current regulations applicable to power
connections, and use at least cable type H05 VV-...
3.3.1 Connecting the BUS connection and temperature
sensor (extra-low voltage side)
▶ If the conductor cross-sections are different, use the
junction box to connect the BUS nodes.
▶ Connect BUS nodes [B] via junction box [A] in star
( Fig. 15, page 96) or via BUS nodes with two BUS
connections in series ( Fig. 19, page 98).
If the maximum total length of the BUS
connections between all BUS nodes is exceeded,
or if the BUS system is realised as a ring structure,
the system cannot be commissioned.
MM100
Maximum total length of BUS connections:
2
•
100 m at 0.50 mm
conductor cross-section
2
•
300 m at 1.50 mm
conductor cross-section
▶ All low voltage leads must be routed separately from cables
carrying mains voltage to avoid inductive interference
(minimum separation 100 mm).
▶ In the case of external inductive interferences (e.g. from PV
systems), use shielded cables (e.g. LIYCY) and earth the
shield on one side. The shield should be connected to the
building's earthing system, e.g. to a free earth conductor
terminal or water pipe, and not to the grounded terminal in
the module.
Only one temperature sensor T0 must be installed
per system. If there are several modules available,
the module that the temperature sensor T0 is
connected to can be freely selected.
When sensor leads are extended, apply the following lead
cross-sections:
•
Up to 20 m with 0.75 mm
section
•
20 m up to 100 m with 1.50 mm
▶ Route cables through the grommets provided and connect
them as shown in the connection diagrams.
3.3.2 Connecting the power supply, pump and mixing
valve and temperature switch (mains voltage side)
The assignment of the electrical connections
depends on the system installed. The description
shown in Fig. 11 to Fig. 14, from page 94
onwards, suggests a possible process for
assigning the electrical connections. Some of the
steps are not shown in black. This makes it easier
to see which steps belong together.
▶ Only use cable of comparable quality.
▶ Ensure the power supply is connected to the correct
phases.
A power supply via an earthed safety plug is not
permissible.
▶ Only connect components and assemblies to the outputs in
accordance with these instructions. Do not connect
additional control units that regulate other system
components.
▶ Route cables through the grommets provided, connect
them as shown in the connection diagrams and secure
them with the strain relief supplied in the scope of delivery
( Fig. 11 to 14, from page 94 onwards).
Installation | 15
2
2
to 1.50 mm
conductor cross-
2
conductor cross-section
6 720 813 621 (2014/12)