Checks Before Commissioning; Checking The Tightness Of Pressure Gas Lines; Checking The Tightness With Nitrogen; Checking The Tightness With Ammonia - Grundfos Vaccuperm VGA-146 Instrucciones De Instalación Y Funcionamiento

Tabla de contenido

Publicidad

Idiomas disponibles
  • ES

Idiomas disponibles

  • ESPAÑOL, página 49

5.2 Checks before commissioning

Check tightness of the total plant before start-up.
– Observe manual of the gas dosing regulators!
Warning
Check the tightness not until the total plant is ready
for start-up.
Danger of gas leakage!
Warning
Before checking the tightness:
Start running the optional built-in liquid trap or the
seperate liquid trap!
Danger of gas leakage!

5.2.1 Checking the tightness of pressure gas lines

Pressure gas lines are all lines from the gas containers to the
vacuum regulator.
If the plant is equipped with a nitrogen rinsing device: Check
tightness roughly with nitrogen (all dosing media)
Detailed checking: with ammonia

5.2.2 Checking the tightness with nitrogen

Close all container valves
Open container connection valves and all shut-off valves up to
the gas dosing system
Open the connection valve of the nitrogen cylinder
Slowly open the valve of the nitrogen cylinder, until the lines
have a pressure of about 10 bar (read at the manometer of the
vacuum regulator).
Warning
Maximum nitrogen pressure 16 bar!
Danger of damages and gas leakage when being
exceeded!
Apply leakage spray or soap water to all components under
pressure
– Formation of bubbles and/or pressure drop at manometer
-->Leakage in pressure lines!
Depressurize the plant!
Eliminate leakage!
Check tightness again!
– No formation of bubbles, pressure at manometer does not
drop significantly within one hour
--> Pressure lines are tight.

5.2.3 Checking the tightness with ammonia

Open all container valves and container connection valves and
quickly close them again
Slowly pass the open ammonia bottle along pressure-gas
leading parts
– Formation of white mist: Leakage in pressure lines!
Depressurize the plant!
Eliminate leakage!
Check tightness again!
Fig. 15 Formation of white mist: Leakage in pressure lines!
– No formation of white mist: Pressure lines are tight.
Fig. 16 Pressure lines are tight
Warning
Liquid ammonia must not come in contact with parts
of the plant!
Danger of leakages by corrosion!
Fig. 17 Liquid ammonia makes leakages by corrosion

6. Operation

6.1 Function

Reducing the gas pressure (overpressure) to subatmospheric
pressure (vacuum)
In case of too high pressure in the device (e. g. if the inlet
valve is soiled or damaged) the overpressure valve opens.
– Gas will be lead to the absorption vessel.
In case of the gas container getting empty or blocked gas
supply (too high vacuum in the device) the vacuum shut-off
valve closes.
– Gas containers will not be evacuated with the injector
vacuum.
Liquid trap (option)
– Prevents liquid gas from getting into the vacuum regulator
– The temperature is self-regulating to max. 60 °C.

6.2 Display Elements

Pressure gauge (option)
– displays the gas pressure at the inlet (admission pressure)
– optionally with a limit contact for minimal admission
pressure, e.g. empty signal is sent to the control panel.
Warning
Do not exceed the admission pressure!
Danger of gas break-out!

6.3 Operating

The device is passive. All adjustment has to be made
Note
at other parts of gas break-out!
Observe manuals of the other components.
17

Publicidad

Tabla de contenido
loading

Tabla de contenido